Digital display for analog signals
Item number: PAX2A Price on request
Delivery time:Delivery time on request
The PAX2A is a digital indicator for analog signals with a two-line display. The 6-digit LED display can be programmed with 3 colors (Red/Ornage/Green). The PAX2A offers functions like tare, summation and linearization etc.. It is also equipped with two function inputs and offers slots for 3 expansion cards. The PAX2A000 is suitable for horizontal installation.
Attributes of Digital display for analog signals
May differ from supplier data
Basic data
Measurement rate, max. 160 Messungen/s
Sensor supply voltage 18 V
Measuring ranges (in °C) -200 to 2,315 °C
Measurement range (V) 2 to 250 V
Measurement range (Ω) 0 to 1,000 Ω
Measurement range (mA) 2 to 250 mA
Number of display digits 6
Measurable quantities / signal type Type K thermocouple Type J thermocouple Type B thermocouple Show all Type E thermocouple Type N thermocouple Type R thermocouple Type T thermocouple Pt100 DC current Resistance/potentiometer Type S thermocouple DC voltage Type C thermocouple Ni120 Cu10
Number of analog signal inputs 1-channel
Parameterizable via Internal keyboard Interface
Type of measurement display LED display
Display properties Two-line display
Housing / Design / Mechanical data / Materials
Dimension (width) 97 mm
Dimension (height) 50 mm
Dimension (depth) 480 mm
Installation/fastening Switch panel installation
Signal inputs/outputs and interfaces
Interfaces/protocols RS-232 RS-485 Profibus DP Show all RS-485 Modbus USB (for programming) DeviceNet
Switching output Relay (2x) Relay (4x)
Analog output signal 4…20 mA 0…20 mA 0…10 V
Approvals / Certificates / Performance level / Integrity level
Approvals/certificates cULus
Product environmental influences (protection class/temperature)
Protection class (front) IP 65
Protection class (housing) IP 20
Electrical data / Signal connections
Signal connection Screw terminals
More functions and options
More functions/options Min/max value display Alarms Password protection Show all Programming lock Scaling via signal application Linearization Display offset, adjustable Filter Analog output signal, optional